The all new Selectronic SP PRO

Proudly AustralianSP PRO Logo

Brought to you by
Selectronic Australia

Copyright © 2009-2011
Selectronic Australia Pty Ltd

 
 
SP PRO SERIES SPECIFICATIONS
SPMC240–AU
SPMC241–AU
SPMC481–AU
SPMC482–AU
SPLC1201–AU
Nominal battery voltage 24 V 24 V 48 V 48 V 120 V
Continuous output power
at 25°C
3000 W 4500 W 5000 W 7500 W 18,000 W
Continuous charge current
at 25°C
105 A 146 A 83 A 125 A 125 A
20 second load rating
at 40°C
7500 W 10500 W 12000 W 18000 W 30,000 W
20 second output current
at 40°C
28 A 40 A 47 A 70 A 110 A
1 minute output power
at 40°C
5400 W 7600 W 8700 W 13000 W 20,000 W
60 minute output power
at 40°C
3200 W 4700 W 5300 W 8000 W 20,000 W
DC input voltage range 20 - 34 V 20 - 34 V 40 - 68 V 40 - 68 V 100 - 170 V
TRANSFER SWITCH
AC transfer current capacity 63 A 125 A
Max AC input source, (generator) W 15 kVA 30 kVA
Max total output to Load, AC source + inverter 15 kVA 30 kVA
AC transfer time no-break
If grid fails 0 - 0.03 seconds
Battery charger type 5 stage, power factor corrected with dual stage float
DC consumption idle 6 W
Standby (adjustable rate) 12 - 20 W n/a
Models
SPMC240–AU
SPMC241–AU
SPMC481–AU
SPMC482–AU
SPLC1201–AU
ON with no load 31 W 36 W 37 W 40 W 75 W
Peak efficiency – all modes 95% 95% 95.5% 96% 96%
10% load 90% 90.5% 91% 91% 91%
20% load 92.5% 93% 94% 94% 94%
50% load 94% 94.5% 95% 95.5% 95.5%
100% load 90% 91% 92.5% 93% 93%
Max Grid Feed capacity rated output
AC OUTPUT standalone
Setting accuracy 210 to 240 V+/- 0.5%
Regulation <1% droop 0-100% rated load
(<2% at 150%, <5% at 200%, <10% at 300%)
THD <3% at 0-200% rated load
Frequency 50 or 60 Hz +/-0.005% standalone
AC SOURCE (input)
Nominal voltage 210 to 240 V~
Tolerance on nominal voltage programmable - 1% to 15%, + 1% to 10%
Nominal input frequency 50/60Hz
Tolerance on nominal frequency programmable +/- 1% to 10%
Generator can be started by battery SoC, DC voltage, battery load, unit temperature, time & remote control
Battery temperature sensor Yes
Mid point battery voltage sensing Yes
Inverter display 22 x LEDs with auto adjusting intensity.
Display indicates: charger status, remaining useable battery capacity, alarms, AC status.
AC status LEDs powered from AC voltage.
Generator control button.
Output mode button.
Alarm silence button.
Digital Inputs 4 x Max 60 VDC ( Active > +6V, Inactive < +3V )
Shunt Inputs 2 x user definable: +/-75mV
Analogue Inputs 2 x general purpose logged 0-60V n/a
Relay Outputs 4 x 60 V, 500 mA
Digital outputs 3 x 60 V, 5 mA
Communication ports 2 x RS232 with adjustable baud rate of up to 57600
Memory retention of settings & data
Permanent
SP LINK configuration and monitoring software Standard.
Allows remote configuration of parameters
and viewing of LED & digital displays
Dimensions (mounted) 345 W x 545 H x 215 D 520 W x 870 H
x 300 D
Models
SPMC240–AU
SPMC241–AU
SPMC481–AU
SPMC482–AU
SPLC1201-AU
Weight 29 kg 34 kg 35 kg 40 kg 105 kg
Circuit Breakers
(AC Source, AC Load)
Double pole 63A Single pole 125 A
Standards AS/NZ61000-6-3 2007
AS62040.1.1-2003
AS4777 2005 (grid connect)
AS/NZS 61000-6-4 2007
AS 4777 2005 pending
Protection IP43
Warranty

5 - 7 years, country dependent. (conditions apply)

Availability Available now
AS4777 Approval Approved and available on the Clean Energy Council list of Approved Grid Connect Inverters
Through a policy of continual improvement, specifications may differ from those shown.
All ratings are at 25°C and nominal battery voltage unless otherwise stated and are correct as at November 2009.